Manufacturing Industry

Client: Manufacturing Industry

The Problem

Thermal fluid sample testing and analysis showed system operating temperatures above the recommended parameters in the header tank of a 60,000 litre Ness thermal fluid system.

What the client wanted to achieve

A lower operating temperature which would fall within the recommended parameters.

The Global Heat Transfer solution

We undertook a Hazardous Operations (Haz Op) Survey which revealed an issue with the routing of some of the pipework. We worked with the client to modify the pipework and drained 33% of the thermal fluid from the system and diluted it with Globaltherm M before re-adding it to the system.

Impact

The operating temperature has been reduced and now falls within the recommended guidelines to provide a durable solution. We continue to monitor the system by undertaking regular test samples and analysis work.

 